Test of cable insulation by increased voltage.
a) test by voltage of industrial frequency. Method of test is selected upon agreement with the manufacturer |
International standard ћЁ 60502-2, 2005 recommends to hold the test with straightened voltage, the duration of application of the full test voltage 15 min.
|
||||||
Rated voltage U, kV |
6 |
10 |
15 |
20 |
30 |
35 |
Test voltage, kV |
14,4 |
24 |
34,8 |
48 |
72 |
80,8 |
After tests it is necessary to earth the conductor for the time not less than 1 hour. |
The test is held by alternating voltage with frequency 0,1 Hz, applied to each phase within 15 minutes.
|
||||||
Rated voltage U, kV |
6 |
10 |
15 |
20 |
30 |
35 |
Test voltage, kV |
18 |
30 |
45 |
60 |
90 |
105 |
|
|
|||||||||||||
Conductor
|
Resistance, Ohms/km, no more at nominal conductor cross-sectional area, mm2 |
||||||||||||
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
|
Cooper |
0,524 |
0,387 |
0,268 |
0,193 |
0,153 |
0,124 |
0,0991 |
0,0754 |
0,0601 |
0,0470 |
0,0366 |
0,0283 |
0,0221 |
If the length of the conductor is different from 1 km and the conductor temperature is different from 20 ∞C, the folloformula of calculation is applied:
where:
L - length of the tested conductor, km. |
Measurement of working electric capacity of cables. After the test it is necessary to earth the conductor and the screen for the time not less than 1 hour.
|